AC/DC Current clamp
The 80I-110s is compatible with any Fluke ScopeMeter Test Tool, Power Harmonics Analyzer, Oscilloscope, Multimeter, or other voltage measurement device that has the following features: BNC input connectors or if using a meter convert the banana plugs to a BNC connector using the adapter PM9081/001.
Current Range: 0.1 to 100A DC or 0.1 to 70A AC
Basic Accuracy (DC to 1kHz):
100mV/A setting: 50mA to 10A +/- 3% of reading + 50mA
10mV/A setting: 50mA to 40A +/- 4% of reading + 50mA
40A to 80A +/- 12% of reading + 50mA
80 to 100A +/- 15% of reading
Output Signal: 10A range: 100mV/A | 100A range: 10mV/A
Bandwidth: 1Hz to 20kHz
Working Voltage: 600V AC rms
Maximum Conductor Size: 11.8 mm (.46 inch) diameter
Safety Rating: IEC 1010 and CSA-C22.2 No. 1010-1 Installation Category II, Working Voltage 600V